Pick the right wire size for the run
This wire size calculator finds the smallest copper or aluminum cable that keeps the voltage drop between the panel and the load within your limit. It works for single-phase AC (230 V or 120 V), three-phase 400 V and DC at 12, 24 or 48 V, which covers solar panels, RV and van batteries and boats. Any other voltage can be typed in.
It also works the other way round. Pick a size under "Size to check" and the tool shows the voltage drop in volts and percent, the voltage at the load and the power lost in the cable. A table repeats the calculation for every standard metric size from 1.5 to 120 mm², and the English version adds the nearest AWG gauge.
How to use it
- Pick a supply with the buttons "230 V single-phase", "120 V single-phase", "400 V three-phase", "12 V DC", "24 V DC" or "48 V DC". For another voltage, edit "Supply type" and "Voltage (V)".
- Enter the load in "Power or current" and choose W, kW or A.
- Set the "Power factor (cos φ)": 1 for a heater, oven or water heater, 0.8 for a motor. The field is greyed out for DC.
- Enter the "One-way length (m)": the distance from the panel or battery to the load, measured once. The formula already counts the return conductor. 100 ft is 30.5 m.
- Choose the "Conductor" and the "Allowed voltage drop (%)". The "3% lighting" and "5% other loads" buttons set the usual values.
Results update as you type, and your last settings are kept in this browser.
The formulas
For single-phase AC and DC, current flows out and back through two conductors: ΔU = 2 × ρ × L × I × cos φ ÷ S. For three-phase, the factor 2 becomes √3: ΔU = √3 × ρ × L × I × cos φ ÷ S. The resistivity ρ is 0.0225 Ω·mm²/m for copper and 0.036 for aluminum, taken at operating temperature. Conductor reactance is ignored.
The tool solves for the minimum cross-section S, then rounds up to the next standard size: 1.5, 2.5, 4, 6, 10, 16, 25, 35, 50, 70, 95 or 120 mm². It also compares the current with an indicative ampacity for each size. When heating calls for a larger wire than voltage drop does, the larger one is recommended and the message says why.
Worked examples
- 230 V circuit, 30 m: 3,680 W is 16 A at cos φ 1, copper, 3%. S = 2 × 0.0225 × 30 × 16 ÷ (0.03 × 230) = 3.13 mm², so 4 mm². The drop is 5.4 V (2.35%) and the cable dissipates 86.4 W. The nearest AWG at least that large is 10 AWG (5.26 mm²).
- 12 V battery: 10 A over 5 m, copper, 3%. S = 2 × 0.0225 × 5 × 10 ÷ 0.36 = 6.25 mm², so 10 mm².
- 120 V garage outlet: 15 A at 30 m, 3%. The calculation asks for 5.63 mm². Checking 12 AWG (3.31 mm²) gives 6.12 V, or 5.1%; 10 AWG (5.26 mm²) brings it down to 3.85 V, or 3.21%.
- Workshop on three-phase: a 9 kW machine at cos φ 0.8, 40 m, 5%. The current is 16.24 A; voltage drop alone would allow 1.5 mm², but heating sets 2.5 mm² (2.03% drop).
- Solar array: 1,200 W over 10 m needs 35 mm² at 24 V but only 10 mm² at 48 V. Raising the voltage cuts the current and the wire size.
AWG sizes in mm²
| AWG | mm² | AWG | mm² |
|---|---|---|---|
| 18 | 0.823 | 3 | 26.7 |
| 16 | 1.31 | 2 | 33.6 |
| 14 | 2.08 | 1 | 42.4 |
| 12 | 3.31 | 1/0 | 53.5 |
| 10 | 5.26 | 2/0 | 67.4 |
| 8 | 8.37 | 3/0 | 85.0 |
| 6 | 13.3 | 4/0 | 107 |
| 4 | 21.2 |
"Size to check" lists every gauge in this table. In North American homes, the usual pairing is 14 AWG on a 15 A breaker, 12 AWG on 20 A and 10 AWG on 30 A. In the UK, 2.5 mm² radials are typically on 20 A and a 6 mm² cooker or charger circuit on 32 A. These are reference points only: the ampacity figures in the tool assume cables in conduit at 30 °C, with two loaded conductors for single-phase and DC and three for three-phase. Buried, bundled or insulated cables run hotter. Electrical work must follow the wiring rules in force; if in doubt, call an electrician.
Frequently asked questions
Why enter the one-way length?
Because that is the distance you measure on a plan. The current goes out on the live or positive wire and back on the neutral or negative one, and the factor 2 in the formula accounts for it.
Should I use 3% or 5%?
3% is the usual target for lighting and 5% for other loads, measured from the origin of the installation. On 12 V systems many people aim for 3% or less, since fridges and pumps cut out early on low voltage.
Why does aluminum need a bigger wire?
Its resistivity is 1.6 times that of copper. For 30 kW three-phase over 80 m at 3% and cos φ 0.9, the tool suggests 16 mm² copper or 25 mm² aluminum.
What do the losses in watts mean?
That is heat produced in the cable, which you pay for. The 86.4 W of the 30 m example is 2.35% of the power; with 6 mm² it drops to 57.6 W.